Precautions for changing the refrigerating oil in the cooling system of the car charger
The cooling system of the car charger should pay attention to the condition of the refrigerating oil during the operation. After the compressor is started, carefully observe the changes in the oil temperature and oil pressure. If the oil changes color, the oil must be changed until the system is clean. Piston refrigerators that are normally put into production and operation must undergo a limited period of maintenance after long-term operation and replace the refrigerating oil.

1. Refrigerating oil replacement operating procedures
1. Close the high-pressure exhaust and low-pressure suction shut-off valves, and use the process valve needle on the compressor to release the refrigerant inside the compressor to make the crankcase of the compressor communicate with the atmosphere.
2. Unscrew the oil drain plug at the bottom of the crankcase, drain the refrigerant oil in the crankcase, and remove the filter for cleaning.
3. Nitrogen can be blown in from the low-pressure inflation valve needle, and the oil drain port can be blocked by hand to increase the pressure in the body, and further remove the residual oil in the body, dry the cleaned filter into the body and tighten the oil drain plug .
2. Refrigerating oil injection
Plan 1: Unscrew the process port plunger on the side of the compressor crankcase, use it as a filling port to pour the refrigerated oil into the crankcase through a suitable tool;
Option 2: (for piston machine) connect the low-pressure pipe of the fluorine-filling meter to the low-pressure process valve needle of the cavity of the piston-type refrigerator, use a vacuum pump to pump the crankcase to negative pressure, and remove the other fluorine-filling pipe separately, one end Insert it into the container containing the refrigerated oil, and connect the other end to the valve needle of the low-pressure suction end of the oil pump, and suck the refrigerated oil into the crankcase by using the negative pressure in the crankcase.
Summary of considerations:
1. You can add a little less when changing the oil, and generally add it to the lower limit of the sight glass.
2. After the refrigerating oil filling is completed, tighten the process plunger or remove the fluorine filling tube, and connect the fluorine pressure gauge to vacuum the compressor.
3. After the vacuum is completed, open the compressor high and low pressure stop valve to check whether there is refrigerant leakage.
4. After turning on the cooling system, check the compressor lubrication and the oil level of the oil glass immediately. If the oil level is lower than the normal range, add refrigerating oil. If necessary, connect an oil pressure gauge to the needle valve of the oil pump to check the oil pressure.
5. The suction side pressure of the oil pump of the semi-hermetic piston compressor should be basically the same as the low pressure suction pressure, and the allowable value of the oil pressure difference.
Matters needing attention:
The refrigerated oil in the cooling system of the car charger is hygroscopic, and the moisture in the oil chemically reacts with the oil. It requires special care when working to minimize the air entering the system and the oil storage container; the refrigerating oil should not be added in excess. If the refrigerating oil is added in excess, There is a danger of liquid shock when the cooling system is reopened.
Verwandte Empfehlungen
-
Selection of heat transfer oil for the refrigeration and heating system of the reactor
1103In the chemical industry, the reactor is a commonly used container, and temperature control is the main quantity to be controlled. The heating and refrigeration cycle equipment of the reactor is an important factor to ensure product quality. The r...
Details anzeigen -
What is the temperature of the cryogenic cooling circulator?
1008The LNEYA cryogenic cooling circulator has a cooling temperature range from -125 degrees to -20 degrees. It adopts a computer cascade temperature controller and a PT100 temperature sensor, and the temperature control accuracy can reach ±0.1 degree...
Details anzeigen -
Description of the principle and mode of industrial water chiller refrigeration cycle
1269Anyone who knows about industrial waterchillers should know that it uses compressors to achieve the cooling effect.So, how does it work when refrigerating?1. Vapor compression refrigeration cycle.After cooling and pressurizing the vaporfrom the...
Details anzeigen -
Precautions for use of LNEYA’s Recirculating chiller
1135LNEYA's low temperature recirculating chillercan be used with supporting instruments (such as rotary evaporators,fermentation tanks, chemical reactors, freeze-drying equipment,biopharmaceutical reactors, etc.), with large cooling capacity and f...
Details anzeigen