How to Solve the Problem of Water Supply in Low Temperature chiller system
Due to the improper operation of low temperature chiller system, there is the possibility of water entering into refrigerant system. Therefore, in view of the problem of water supply in low temperature chiller system, process guidance is formulated to serve as a reference for maintenance.
1. Analyse the reasons. Check the whole low temperature chiller system to confirm the cause of freezing damage and find out the leak point.
2. Blow dirt in sections.
(1) First, air compressor can be used to blow water (save nitrogen), until no water mist precipitate. Then blow with high pressure nitrogen, at the same time, heat the nitrogen (the nitrogen cylinder is prohibited from heating).
(2) Because the pipeline of low temperature chiller system is complex, water can be blown out in segments by using welding torch in some parts according to specific conditions.
(3) Heat and dry. The capillary, thermal expansion valve, compressor and other small components can be placed in the oven to bake and dry. Do replace the refrigerating oil in the compressor after the water is dried.
1. Vacuum drying
(1) Restore the pipeline and maintain the nitrogen pressure to ensure the air tightness of the system. Then connect the vacuum pump to the system for vacuum drying. (Dry filter barrel should be added to the front end of vacuum pump to avoid excessive water and gas entering the vacuum pump)
(2) In the process of vacuum drying, heat the place where water is easily stored in the pipeline, and the time can be determined according to the site.
2. Debugging and running.
(1) Make sure that the water in the system is basically removed.
(2) Connect the external drying filter barrel to the system and replace the desiccant after running for 5 minutes. At the same time, observe the operating parameters of the unit and pay attention to the sound of the compressor. If the dry filter is cold, the expansion valve frosts, and there is a pressure difference of more than 0.5 kg before and after the return air filter, stop the compressor immediately.
3. Completion of maintenance
(1) Remove the refrigerant pipe from the drying filter barrel and restore it.
(2) Check the supplementary refrigerant quantity. Turn on and check the machine running parameters to confirm normal.
Verwandte Empfehlungen
-
Häufige Fehler und Ursachenanalyse bei luftgekühlten Kühlern
1185Während des Einsatzes von luftgekühlten Kältemaschinen ist es unvermeidlich, dass einige allgemeine Fehler auftreten. Die Benutzer müssen die möglichen Fehlerursachen verstehen und rechtzeitig entsprechende Lösungen finden, um die Produktion und den Betrieb stabiler zu machen...
Details anzeigen -
How to choose a manufacturer with low failure rate 3p freezer?
948There are many factors in choosing a 3p freezer, and users should be cautious when choosing a manufacturer. Choose a 3p freezer with a low failure rate to reduce operating costs. When running a 3p freezer, the cost of using a 3p freezer will conti...
Details anzeigen -
What references are needed for the selection of reactor temperature control system?
1070The heating power selection of the reactor temperature control system is roughly based on the size of the reactor. The reactor temperature control system is a constant temperature device used to heat and cool the reactor. When selecting, the two ...
Details anzeigen -
Einführung in Niedertemperatur-Kühlgeräte
1141Low Temp Chiller ist eine Art von Kühlgeräten, die Kältequelle unter 0℃ zur Verfügung stellen kann. Es bezieht sich im Allgemeinen auf die Verwendung Temperatur von 5 bis 35℃. Das Kältemittel kann durch Ethylenglykol oder Calciumchlorid wässrige Lösung getragen werden, und die...
Details anzeigen