1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Verwandte Empfehlungen
-
What are the installation requirements for lithography chillers?
1081In order to ensure the reliable and normal operation of the chiller of the lithography machine and prevent the failure of the chiller caused by improper water distribution pipeline construction, the following matters should be paid attention to wh...
Details anzeigen -
Where do you need explosion-proof water chillers?
845Explosion-proof refrigeration unit water chillers (explosion-proof chillers) are mainly used in environments with explosion risks to ensure the safety and reliability of the cooling process. This type of equipment is specially designed to ...
Details anzeigen -
Battery test chiller operation evaporating temperature description
1228In the current new energy vehicle battery test equipment, the use of more batteries to test the chiller evaporation temperature has a certain impact on the equipment, then what is the specific impact? When the battery test chiller heat load increa...
Details anzeigen -
Introduction of LNEYA Semiconductor Temperature Test System
1195The semiconductor temperature test system is an indispensable part of the semiconductor process. The LNEYA semiconductor temperature test system is dedicated to various semiconductor tests. The semiconductor temperature test system runs through th...
Details anzeigen