Explosion-proof ultra-low temperature refrigerator internal leakage instructions
1. Sound leak detection method:
First, the refrigeration pipeline of the explosion-proof ultra-low temperature refrigerator is filled with nitrogen. Then use a stethoscope to check the interior. When you hear a leak in a certain area, mark it. Carefully pry open the metal plate at that place, check the leak point of the pipe with thick soapy water, repair by repair welding or gluing, fill the foaming agent, fill the mouth with a larger metal plate, and glue the four sides. . This method is incapable of causing micro-leakage in the refrigeration system, and is likely to cause false detection or missed detection.
2. Evaporator replacement method:
After the evaporator leak is determined, replacement repairs are performed using a finished evaporator that can be loaded into the interior of the original evaporator. Connect the new evaporator of the explosion-proof ultra-low temperature chiller to the original refrigeration line, and replace the new capillary and dryer. The disadvantage of this method is the high cost, which is powerless when encountering evaporators with special shapes or multi-door machines and leaks in the refrigeration tubes.

3. Copper tube coiling method:
This is a suitable repair method for leaks of any type of explosion-proof cryogenic refrigerator. Generally, the size of the purchased copper pipe is calculated first, and the shape and length of the copper pipe are determined according to the size of the inner casing.
4. Re-foaming maintenance method:
During the overhaul, it is necessary to open the back panel of the cabinet and dig out the original foaming material of the explosion-proof ultra-low temperature refrigerator. After exposing the evaporation tube, it is filled with nitrogen to check for leaks. Pay special attention to each connection solder joint when detecting leaks. This repair method is suitable for the case where the refrigeration system has a connector on the back, and is not suitable for the occurrence of internal leakage in the refrigeration pipe having a leak point at a deeper level. After the leak is detected, repair welding or repair with a glue pool, then re-foam and make up the back plate.
These methods of explosion-proof ultra-low temperature refrigerators can basically find out the cause of the internal leakage and solve them well.
Verwandte Empfehlungen
-
Minimum 40 degree refrigerator use precautions
1123The temperature of the lower 40 degree refrigerator is indoor temperature: 5-32 °C, relative humidity 80%/22 °C, the distance from the ground > 10cm, the altitude below 2000m, the safe environment guarantees a smoother operation of the lower 40...
Details anzeigen -
Advantages and disadvantages of water-cooled chillers
1077The water-cooled industrial chillers produced by LNEYA are refrigeration equipment that provides chilled water. Today we will discuss the classification, advantages and disadvantages of water-cooled chillers. Water-cooled chiller configuration: 1....
Details anzeigen -
Umwelttechnische Beschreibung eines Kondensators für große industrielle Gefriergeräte
1098In industrial cold processing, large industrial freezers are one of the more used equipment. Among them, the condenser is one of the main components, and its performance is very important. Therefore, when choosing, everyone still needs to understa...
Details anzeigen -
Fault Hint of Cryogenic Chiller Refrigeration System
926When the high and low pressure of the system are higher than normal, there is usually air or excessive refrigerant in the system. At this time, we need to re-vacuum, and then add a proper amount of refrigerant to solve this problem. But there are ...
Details anzeigen